Mr. Harmonics

Mr. Harmonics is frequently being blamed when an equipment failed (or when a cable burnt, capacitor bank blown, or a circuit breaker tripped without an obvious fault). Some without due consideration of other simpler factors will blame Mr. Harmonics and his cousins like Mr. Resonance (or perhaps his friend, Mr. Transient – story for another day) straightaway.

Surprisingly, it is a fairly easily accepted reason here. And with power quality instruments getting more affordable these days, it has been becoming quite common to see someone using this new toy, measure current harmonics in percentages of 50-80%, and straightaway concluded that it is indeed a harmonics problem.

Firstly, when it comes to harmonics, we need to know; is it voltage or current harmonics? While there is a common indicator to measure both of them – using the Total Harmonic Distortion (THD) formula (RMS value of the harmonic content expressed as a percentage of the fundamental), one needs to know the pros and cons of using such indicator when applying to voltage/current harmonics.

Usefulness of THD

  • provide a good indication of how much additional heat will be realised when a distorted voltage is applied across a resistive load
  • give indication of the extra losses caused by the current flowing thru a conductor

Limitations of THD

  • unreliable indicator of voltage stress within a capacitor (look out for the peak value instead not THD)
  • a meaningful indicator for voltage harmonics, as voltage varies only a few % (as referenced to its fundamental)
  • not so the case for current harmonics as a small current may have high THD but not a significant threat to the system; can be extremely misleading.
sample Iharmonic waveform/spectrum
Fig1. sample Iharmonic waveform/spectrum

Here in Fig1, is the current waveform and spectrum of the common switched-mode-power supply to our PC/laptop at work or home. Looking at just its THD% current, one will be extremely alarmed (162%!!). So should all of us purchase harmonic filters for all our homes/offices then? (fact: the actual amperes of this circuit is less than 0.6Amps, and VTHD  is only 1.52%)

When it comes to current harmonics, it will be more meaningful to use other alternative indicators such as Total Demand Distortion (TDD), or use absolute amperes (my personal recommendation).

Fig 2 and 3 shows the trending results of current harmonics, presented in THD%, Harmonic Amps and TDD%.

Total Demand Distortion

  • Current THD is misleading during light load conditions (when I1 is small)
  • Similar to THD, except that the distortion is expressed as a percentage of some rated load current magnitude rather than as a percentage of the fundamental.

 

Fig2. In THD%
Fig2. In THD%

 

Fig3. Harmonic Amps and TDD%
Fig3. Harmonic Amps and TDD

Transmission Code Clause 6.7.4b

It was reported that the voltage disturbance (lasting about 100ms) yesterday at about 1418hrs was caused by lightning affecting the inter-connector link between Singapore and Johor, Malaysia. Link from the statement by SP PowerGrid.
(FYI: Singapore is inter-connected to Johor at 230kV – a transmission level voltage; any disturbance at this level will typically be ‘seen’ by everyone in Singapore with 1/4 of the island ‘seeing’ the worst dip values).

While there is hardly any blackout moments in Singapore due to how the grid is designed and operated here, voltage dips like the above can actually be quite common. In the last 6 months, there has been 3 of such transmission level-originated voltage disturbances (as taken from our monitoring records; 5/11, 10/9 and 27/7). As electrical faults in the grid (be it caused by cable damage, customer’s installation fault, utility equipment fault or lightning) cannot be totally eliminated (only reduced thru rigorous maintenance, regulations/enforcement etc), customers with sensitive equipment should take measures in protecting their equipment adequately. They should also be aware of this Clause in the Transmission Code (which is also in their Connection Agreement with the Utility).

equipment immunity
equipment immunity

This clause basically rules out any ‘compensation claim’ from the Utility due to losses sustained arising from voltage dips. To some, this may seem ‘cruel’, but I believed this clause is fair as the electrical network is interconnected and everyone (Customers, Utility, Gencos) has to play their part. From my experience, the awareness on the need and know-how for protection against voltage dip is still very much work-in-progress here in Singapore. The key to solve voltage-dip related problems is not to seek compensations, but rather to undertake a proper assessment on the vulnerabilities of their equipment against voltage dips and then invest in the right mitigation solutions / methods.

 

“Explaining the outage, SGX said power is supplied to the data centre from two separate substations, which is then connected to the individual UPS systems. A “momentary fluctuation in power supply from the substations” caused the UPS systems to switch to its internal power source, but these power sources malfunctioned.” – ChannelNewsAsia.

 

Voltage Disturbance – 5-11-2014 1418hrs

In the early afternoon today, there was a voltage dip recorded at approximately 1418hrs (2:18 PM). A snapshot of this dip waveform captured in one of our sites in Bedok area is shown below. We also received several calls from various sites scattered over the island, reporting chiller operations being affected, etc.  These could only mean one thing; a transmission level (eg. 230kV) fault had occurred.

Voltage Dip 5-11-2014hrs
Voltage Dip 5-11-2014 1418hrs

 

Coincidentally, a report from ChannelnewsAsia reported an incident at SGX at approximately the same time, as shown in the following news snapshot. Without knowing further detailed information, I cannot really confirm / comment if these two incidents are related.

Voltage dip, while it typically occurs for just a slight fraction of a second may result in serious consequences when critical sensitive equipment are not being adequately protected. Usually, semiconductor plants suffer the most in these type of incidents, as their process equipment etc are very sensitive to variations in the power supply.

Voltage dip mitigation comes in various forms; some are battery-based like the the UPS (which is also a mitigation against a total blackout), while others are batteryless like the SoftSwitching MiniDysc (which caters for variation in the power supply for a few seconds only). The latter is preferred for dip mitigation as batteries require a rigorous maintenance and replacement programme, to ensure the batteries do work when they are called for.

CNA 1418hrs
CNA 1418hrs

Voltage Disturbance – 10-9-2014 1919hrs

Earlier, our office recorded a ‘shallow’ dip at approximately 1919hrs.  Tell-tale signs from other neighbouring monitoring sites show this could be a transmission-level fault. Shall await for the report from the utility tomorrow.

Update 15/9/2014 from the Utility: Customer installation fault at Jurong Island

Noting how this dip due to a ‘customer installation fault’ can be seen in many areas, those ‘in the know’ will know who is the Customer here.

voltage waveform captured at LV - 230V
voltage waveform captured at LV – 230V

230kV Voltage Dip 27-07-2014 09:25 AM

Just awhile ago, if you are one of the facilities’ guys, you probably had to scramble around because of dip alarms, standby generator cutting in or chiller drop-off.

Another 230kV fault was registered; affecting the South side of Singapore the most, suggesting a 230kV fault in the South block.

Here is a voltage waveform from one of our sites in the South.

Voltage waveform is taken at Low Voltage (L-N). It will mirror what is seen at 22kV and above (L-L).
(i.e L1 phase at LV is equivalent to L1L2 at 22kV).

The waveform here shows that there was a single phase fault (L2) at 230kV.

230kv dip 27-07-2014 0925hrs

Here it was registered; worst case dip of more than 50%. Other blocks in Singapore (North, West, East) would also have seen this fault, albeit at less severe values.

On a happier note, Selamat Hari Raya Aidilfitri (in advance) to my fellow Muslims. Maaf Zahir Batin.

Voltage Dip & Its Mitigation – An Overview

In Singapore, a voltage dip is defined as per EN50160; “a sudden reduction of the supply voltage to a value between 90% and 1% of the declared voltage, followed by a voltage recovery after a short period of time; between 10ms and up to a minute”. Typically it lasts less than 200ms. Two things matter in the definition of a dip. See Figure 1.

1)      Magnitude: This typically reflects the fault severity and also the proximity of the monitoring point to the fault location.

2)      Duration: The timer starts when the voltage falls below the 90% threshold and ends when all voltages are equal to or above the 90% threshold. This is very much dependent on the time taken to isolate the fault and the nature of loads connected.

Fig1: Definition of a Voltage Dip
Fig1: Definition of a Voltage Dip

The Utility company here has a power quality monitoring system in place; from voltages 22kV and up to 400kV.  As these are 3 phase 3 wire systems; line to line voltages are used in the definition of a dip.  When there is such a dip, the worst dip by magnitude and its duration will be published by the Utility.

There is a significance of such definition being used in the 66kV and 22kV networks, whereby it is a resistively earthed grounded system (thru the neutral ground resistor). Here, a single phase fault will not be a registered as a voltage dip as the other two non-faulted phases will swell; ‘compensating’ the faulted phase. This will result in a drop of voltage (line to line) of usually less than 10% (hence not a dip). The Utility company here described such events as ‘Voltage variation’.

In recent times, voltage dips seem to be quite frequent in our office at 16 Boon Lay Way, Tradehub21. Tradehub21 is one of the many commercial buildings located in this Jurong East region; near to the International Business Park and also shopping malls like IMM, JCube, JEM and Westgate.

In the last 5 months, our office has recorded a total of 3 voltage dips; two originated from the Utility’s 230kV transmission fault and one which occurred last Friday due to a 22kV Customer’s Installation fault (along Jurong Gateway Road). It is fortunate in a way that this area is not a Semiconductor Hub, as just one dip will have costly implications on a semiconductor plant, let alone three.

Fig2: Voltage dip (dip by 80%) 21-03-2014 0650hrs (QPM Office – seen at 230V).  A three-phase 22kV fault; Dip magnitudes at 22kV will be similar.
Fig2: Voltage dip (dip by 80%) 21-03-2014 0650hrs (QPM Office – seen at 230V).
A three-phase 22kV fault; Dip magnitudes at 22kV will be similar.
Fig3: Voltage dip (dip by 43%) 31-12-2013 1905hrs (QPM Office – seen at 230V). A single phase 230kV fault; 22kV dip waveforms and magnitudes will be largely similar due to the proportionality between a 22kV line to line voltage and a 230V line to neutral voltages (Dyn11).
Fig3: Voltage dip (dip by 43%) 31-12-2013 1905hrs (QPM Office – seen at 230V). A single phase 230kV fault; 22kV dip waveforms and magnitudes will be largely similar due to the proportionality between a 22kV line to line voltage and a 230V line to neutral voltages (Dyn11).
Fig4: Same voltage dip event as Figure 3 but seen at 22kV at a QPM-managed site near Gul area. 230kV Singapore Grid is solidly earthed; hence during a single phase fault, the other two non-faulted phases will also drop slightly. Here was an L1 (red phase fault); affecting L1L2 and L3L1 significantly. Hence you can notice both L1L2 and L3L1 ‘dropped’.
Fig4: Same voltage dip event as Figure 3 but seen at 22kV at a QPM-managed site near Gul area. 230kV Singapore Grid is solidly earthed; hence during a single phase fault, the other two non-faulted phases will also drop slightly. Here was an L1 (red phase fault); affecting L1L2 and L3L1 significantly. Hence you can notice both L1L2 and L3L1 ‘dropped’.
Fig5: Voltage dip (dip by 48%) 30-10-2013 1413hrs (QPM Office – seen at 230V). A single phase 230kV fault.
Fig5: Voltage dip (dip by 48%) 30-10-2013 1413hrs (QPM Office – seen at 230V). A single phase 230kV fault.

However, this is not to say that commercial buildings and shopping malls are immune to the effects of voltage dips. Here are the common known effects of voltage dips in a commercial building / shopping mall setting.

1)      Chiller System

It is a known fact that chillers plants and its related equipment are sensitive to voltage dips. Relays, control contactors and the electronic/computerized controls may drop off during  dips, hence causing the trip. The impact to building occupiers is small; as these effects are likely to be transparent to them; or at most minor discomfort due to a slightly raised ambient temperature.

Possible Mitigation

The sensitivity is sometimes made intentionally (and at times over-conservative) as there is a concern on possibilities of damage to the motor due to the high transient current upon normalization of system voltage (hence it is better to trip). A consultation with the Chillers’ OEM is almost necessary if one decides to protect its control circuits. This is to ensure that it will not result in damaging the motor.

Chiller controls can be secured with on-line UPS or voltage dip mitigation solutions like MiniDySC from SoftSwitching Technologies. Sensitive relays can be identified and replaced. Another option is to enable the Chiller for ‘Auto-Restart’ function if allowable.

Having an internal thorough proper restarting procedure of chillers in the event of tripping due to voltage dips in the network is also a form of ‘mitigation’ as it reduces the downtime of the Chillers. This usually needs close co-operation with the Utility company or install a permanent power quality monitoring system in the building to determine where the origin of the voltage dip (internal fault or fault from the Grid).

2)      Lighting Circuits

During a voltage dip, flickering of the lights can be observed. In general, problems only arise when High Intensity Discharge (HID) lamps are used. These types of lightings are known to be sensitive to voltage dips and temporarily extinguish after a voltage dip. Re-ignition time usually takes up to 10 minutes.

Possible Mitigation

For HID lamps applications, one possible mitigation is to re-fit with “hot re-strike” igniter for instant lighting restoration.  In the use of HID lamps in “critical areas”, it is best to deploy them alongside normal type of lightings (for eg. Fluorescent lightings), so as to avoid a ‘total blackout’.

In addition, occurrence of voltage dip across three phases is rare; hence the even distribution of lightings across the 3 phases can avoid a ‘total blackout’ during a voltage dip.

3)      Escalators

During a voltage dip, the control contactors and PLC of the escalator may drop off. Another cause could be the activation of the phase monitoring relay, which is meant to activate upon loss of mains.

Governed by the Singapore Standard CP15:2004, escalators are designed to be brought to rest in a largely uniform deceleration in the event of loss of mains (thus not a safety concern). However public image may be affected.

Possible Mitigation

The control contactors and PLC can be secured through adding an uninterruptible power supply (UPS) and the phase monitoring relay can be upgraded to a relay equipped with a time delay for up to 0.2 sec. See Figure 6. This is based on CLP Power Hong Kong’s experience in voltage dip mitigation for escalators. It is also documented in Hong Kong’s” Code of Practice on the Design and Construction of Lift & Escalator.”

Fig6: Simplified SLD of Escalator Control – Recent Development in Power Quality by Dr F.C Chan (CLP Engineering Limited)
Fig6: Simplified SLD of Escalator Control – Recent Development in Power Quality by Dr F.C Chan (CLP Engineering Limited)

My personal accounts in conducting voltage dip tests on some of these escalators showed that in general, a voltage dip of more than 40%, regardless of duration that affects the supply to the control circuits will result in the escalator to stop. Mitigation equipment such as the MiniDySC was found to be an effective solution against such events.

A full implementation of such mitigation however will need further tests with the OEM escalator’s specialists to ensure that safety features related to its braking will not be compromised. Additionally, it may also require slight deviations from the existing CP15 as similarly re-defined in Hong Kong’s Code of Practice for Lifts & Escalators.

4)      General Circuits

General circuits served by miniature circuit breakers (MCB) have also been reported to have tripped after a voltage dip. Immediately after a voltage dip, some MCBs may tripped due to large in-rush current drawn by motors, switch mode power supply, circuits containing control transformer, etc.

Possible Mitigation

Normally, if the MCBs are properly sized to cater for such ‘inrush’, the circuits should not trip.

SEMI F47

When it comes to voltage dip mitigation, the word “SEMI F47” will most likely to crop up. Without going into details, it is basically a minimum ride-through specification for semiconductor tools and processes as the semiconductor industry are most prone to voltage dips due to the nature of its operations. See Figure7.

However it must be noted that even such specification does not translate to 100% availability during a voltage dip as dips that are required for compliance with this specification occur between one phase and neutral, or between one pair of phase, at a time only. Hence for these 3 voltage dip incidents mentioned, a SEMI F47-rated equipment will also not guarantee you 100% availability.

Fig7: SEMI F47 0706 – Specification for Semiconductor Processing Equipment Voltage Sag Immunity
Fig7: SEMI F47 0706 – Specification for Semiconductor Processing Equipment Voltage Sag Immunity

To put in simply, in the SEMI F47 specification, an economical balance has been chosen such that semiconductor processing equipment which meets the requirements will be immune to most, but not all, real-world voltage dips at semiconductor plants.

Similarly if one is to consider mitigation equipment, a cost-benefit analysis has to be conducted as such mitigation do not come cheap. A historical dip statistics of the area from the Utility Company should always be among the first things to be obtained.

Fig8: Cost-Benefit Analysis
Fig8: Cost-Benefit Analysis

Faults (and hence voltage dips) are inherent in all power systems in the world. The frequencies of such occurrences can be minimized but not eliminated. Minimization requires the cooperation of all Stakeholders; the Regulator, the Utility company, the Licensed Electrical Engineers and Customers alike through regulations, regular preventive maintenance and condition monitoring.

And if need be, voltage dip mitigation equipment can be employed for those with sensitive operations or processes, albeit it will come at a price. But the price of leaving it to chance may even be greater (see Figure 8). Ultimately the user has to decide.

Voltage Dip 21/3/2014 0650hrs

Earlier in the morning, our office (in Jurong East) captured a voltage dip of about 80%.  See Figure 1 (3 phase fault – seen at Low Voltage)

Figure 1: Dip Office 21-03-2014 0650hrs
Figure 1: Dip Office 21-03-2014 0650hrs

Another monitoring site in Gul area also monitored a variation as seen in Figure 2. It was likely to be a distribution level (22kV) fault.
Update: Official source said it was due to a Customer Installation fault at Jurong Gateway Road

Figure 2: Voltage variation 21/3/2014 0650hrs
Figure 2: Voltage variation 21/3/2014 0650hrs

Saving Energy Thru Voltage Reduction

Introduction

In Singapore, low tension voltages supplied by the utility has to meet the voltage regulation limits of +/-6% of 230V (single phase) / 400V (three phase). While this is usually the case, there will be times when voltages can be excessively high during low loading periods primarily in areas whereby there are a large proportion of commercial or industrial blocks.

While equipment’s ability to handle steady state voltage variation varies from one equipment to another, in general any equipment which is constantly ‘exposed’ to long periods of overvoltages will suffer from a reduced lifespan. IEC TR 61000-2-14 showed a reduced lifespan of almost 50% when a filament lamp was operated at 5% higher than its rated voltage. Though it will not be as severe for other types of lightings, one should still expect shorter lamp/ballast life.

And with ‘energy savings’ being the buzz words these days, one may consider to reduce the voltages as ‘seen’ by the equipment even further. This is where voltage optimisation comes in. The interest on how reducing voltages can be used to save electric energy has been around for many years now. The results however have been mixed as its effectiveness is very much dependent on the type of loads and its applications.

In general, loads can be categorized into  3 Types;
i) Constant impedance:
Power is proportional to (Voltage)2 .
ii) Constant power:
Demand is constant regardless of Voltage.
iii) Constant current:
Demand is proportional to Voltage.

Its relationship to voltage & loading is shown in Figure 1.

Actual demand created by "1 kW" of each of the 3 Types of Loads, as a function of voltage supplied to them – Source: Power Distribution Planning Reference Book (H.Lee Willis)
Figure 1: Actual demand created by “1 kW” of each of the 3 Types of Loads, as a function of voltage supplied to them – Source: Power Distribution Planning Reference Book (H.Lee Willis)

Trial Setup

An area in our office was recently equipped with such energy savings device, for the lightings. In our trial, it basically functioned like a “step-down” transformer, reducing the voltage to the lighting circuits. The device has 3 voltage reduction levels; each is a ~13V step down from the incoming voltage.

 

Figure 2: Energy Savings Device
Figure 2: Energy Savings Device

Two sets of Fluke 435 Power Quality Analyzers were also installed, monitoring the input and output of the energy savings device; when it was operating at 3 different voltage step levels. Its aggregation interval was set at 1 second and measurement was recorded for 1 hour for each voltage step level.

Figure 3a: Trial Setup
Figure 3a: Trial Setup

 

Figure 3b: Area Under Test
Figure 3b: Area Under Test

Lux readings were also taken at various spots in the area, for comparisons against the following guidelines to ensure resultant lux values did not go lower than the recommended levels.

Table 1: Selected Lux Levels Guidelines

Guidelines Recommended Lux Levels
AS/NZS 1680.2.2 –  Recommended Lux level for general office tasks

320 lux

HK Occupational Safety & Health – A guide to work with computers – Recommended illumination for computer desk work

300-500 lux

SS CP87 2001: Industrial Illumination – Recommended Lux level for routine office work

320 lux

Results

Table 2: Measurement Results (selected)

Parameters
* measured at input
Without energy savings device Step 3
(reduction of approx 39V)
Voltage 238.94V  – 242.02V 238.49V – 240.44V
Current 8.778A – 9.03A 5.197A – 5.272A
Power 1207.437W – 1249.052W 811.404W – 825.791W
Power Factor 0.57 – 0.58 0.65
Energy Consumed 1.239 kWh 0.818 kWh

Interestingly, most occupants (with the exception of one person) working in this affected area did not notice the dimming of the lights.

In this short trial, the reduction of the voltage to ‘Step 3’ (which resulted in the dimming of the lightings – lux value reduced by 53 lux on average) achieved a 34% of savings in kWh consumption.

Conclusion

Voltage reduction does bring savings in energy, if applied on the right load and application.

Before one decides to use such devices, it is important to check what type of loads will be connected. As seen in Figure 1 earlier, not all loads will benefit in terms of energy savings when voltage is reduced. Even in cases of lightings, not all types will be suitable.

Its application matters as well. There is little benefit if resultant lux level becomes too low and the employee has to use a desk lamp to complement the office lightings. Or that an equipment has to operate longer to achieve the same objective (eg.  A kettle to run longer to boil the same amount of water, under a reduced voltage state).