Portable Residual Current Devices

In Singapore, all socket outlets intended for use by ordinary persons and are intended for general use needs to have RCD protection, with rated residual operating current of not more than 30mA.

In addition, the 30mA RCDs (type AC and A) used here have faster tripping time requirements, as shown below.

It is also a common practice in both industrial and commercial work settings, that the premises’ owner requires the vendor/contractor to use portable RCD (PRCD) whenever an electrical appliance / equipment is being connected to the socket outlet.

PRCD is designed to be plugged into any standard socket-outlet. An appliance / equipment can then be plugged into it. It provides additional protection against electrocution to the person in contact with the appliance/equipment (and its cable/wirings). Typical trip ratings are 10mA and 30mA.

Examples of PRCDs

It is sometimes taken for granted that this PRCD will trip first before the Distribution Board’s RCD when there is a fault at the particular appliance/equipment. While this is the ideal outcome, it is not necessarily so even if one were to use a 10mA PRCD.

Here, three numbers of 10mA PRCDs were tested under different scenarios.

RCD Trip Tests Using Fluke 1663 Multifunction Tester
Note: The Distribution Board has a background leakage current of about 6 to 7mA.
Test at Rated (0 degrees)
Test at Rated (180 degrees)

These simple tests have shown that it is possible for the Distribution Board’s RCD to trip due to a fault at the ‘PRCD-protected’ appliance/equipment.

It very much depends on

  • Background leakage current at the Distribution Board
  • Leakage / fault value at the appliance/equipment
  • Trip characteristics of the Distribution Board RCD and the PRCD

Trip Down Memory Lane – 13 October 2000

On October 13, 2000, the Public Utilities Board announced, “New Measures to Control Voltage Dips”, which went effective on 1 November 2000.

The new measures include reviewing a licensed electrical engineer  (LEE)’s performance if the electrical installation(s) under his charge had caused a total of 3 voltage dips, within a period of 2 years.

This was the beginning of having all voltage dip incidents (date, site, LEE-in-charge) published on the Authority’s website.

From The National Archives Singapore

Then, the utility’s (PowerGrid) power quality section, the Power Quality and Load Analysis (PQLA) section, was just being formed. The island-wide power quality monitoring system (PQMS) was still in the works. It became operational somewhere in 2001-2002 with 80+ PQ monitors monitoring voltage levels from 22kV to 230kV.

Singapore’s 230kV transmission network was just being split into two networks, effectively minimizing the impact of a 230kV voltage dip from one another.

Voltage dip, then and now is still a costly affair for sensitive industries. While just lasting in terms of milliseconds, it can have a detrimental impact on production processes, especially those in the semiconductor-related industries.

The utility via its subsidiary (SP Systems) introduced (shortly after in October 2002), a voltage dip mitigation device, known as the Dynacom. It was a single-phase ultra-capacitor-based device meant to compensate voltage dips as low as 40% of nominal and for up to 1 second.  It was targeted at protecting sensitive control circuits.

SP Systems Dynacom
SP Systems Dynacom

Fast track to today and the number of PQ monitors has more than doubled. The PQMS has enabled the utility to keep track and map out its voltage dip performance (System Average RMS Frequency Index – SARFI map) to the various regions of the island.

An Old SARFI map
An Old SARFI map

Singapore’s 230kV transmission network has since being split into 4 parts, limiting the significant impact of a 230kV voltage dip to just 1/4 of the island.

With inter-connectivity to our ASEAN neighbours being the talk of the town these days to improve the reliability of the electricity grid, we must not forget it does come with some downside as well.

Being inter-connected, any fault that occurred in one country’s electrical network can be seen in another. For instance, right now, Singapore is connected to Malaysia at 230kV. Any faults on either side of the network will be seen by both.

Here, in a recent event whereby a Tenaga Nasional Berhad (TNB)’s transformer was reported to have tripped. It had caused a voltage variation here in the eastern part of Singapore.

22kV Voltage Variation 8/9/2021 0432hrs